Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 258

Advertising
background image

Parameters B-83

1503-UM054C-EN-P – June 2013


Jog Time for IB5 [IB 5 Jog Time]

Parameter Number:

152,_,_,_,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-5-21

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

30

Default Value:

12

This parameter allows the user to view and set the Jog Time for

contactor IB5. It indicates the amount of time that a contactor can be

Jogged (momentarily closed) for. This is only for Electrically Held

contactors and makes use of the Open command. See Temporary

Jog Function in Chapter 4 for a more detailed description of this

feature.


Jog Repetition Time for IB1
[IB 1 Jog Repetition Time]
Parameter Number:

153,129,105,81,56.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-1-22

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

60

Default Value:

6

This parameter allows the user to view and set the Jog Repetition

Time for contactor IB1. It indicates the amount of time between

successive Jog intervals. Therefore, once a Jog interval has begun, it

cannot be repeated until the Jog Repetition Time has elapsed for

contactor IB1. This is only for Electrically Held contactors and

makes use of the Open command. See Temporary Jog Function in

Chapter 4 for a more detailed description of this feature.