Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 215

B-40
Parameters
1503-UM054C-EN-P – June 2013
Discrete Output Point Fault Action [DOP Fault Action]
Parameter Number:
72,60,48,36,23.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0x1E-1-7
Group:
Control
Units:
-
Minimum Value:
0 = Go to Fault Value
Maximum Value:
1 = Hold Last State
Default Value:
0
Describes the action on the occurrence of a DOP fault.
Discrete Output Point Fault Value [DOP Fault Value]
Parameter Number:
73,61,49,37,24.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0x1E-1-8
Group:
Control
Units:
-
Minimum Value:
0 = Off
Maximum Value:
1 = On
Default Value:
0
Dictates if any extra action will be performed on the occurrence of a
DOP fault.
Discrete Output Point Idle Action [DOP Idle Action]
Parameter Number:
74,62,50,38,25.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0x1E-1-9
Group:
Control
Units:
-
Minimum Value:
0 = Go to Idle Value
Maximum Value:
1 = Hold Last State
Default Value:
0
Describes the action on the existence of a DOP idle condition.