Table 8.f – power-up safety configuration, Dip sw2, Power-up safety – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 110: Enabled, Future use, Mc board dip switches

Configuration/Programming 8-5
1503-UM054C-EN-P – June 2013
This function is useful for applications that require a contactor to re-
close after a voltage dip or voltage loss.
This setting is used exclusively to determine the Power-up safety
mode. It cannot be set on the IE module, but can be read from the IB
module.
Table 8.F – Power-Up Safety Configuration
Power-up Safety
DIP SW2
6
Enabled
OFF
Disabled
ON
Future Use
These DIP switches are not used and are for future use.
Table 8.G – Future Use
Future Use
DIP SW2
7
8
Not used
OFF
OFF
Not used
OFF
ON
Not used
ON
OFF
Not used
ON
ON
MC Board DIP Switches
Some of the functionality of the IntelliVAC MC product is derived
from the settings of the DIP switches on the MC board.
The DIP switch settings are only read once after a power up
sequence occurs. If changes are to be made to the DIP switch inputs,
then control power must be recycled before the changes will take
affect.
Figure 8.2 – MC Board Configuration DIP Switches