Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 347

Advertising
background image

B-172

Parameters

1503-UM054C-EN-P – June 2013

Contactor Coil Current for IB4
[IB 4 Contactor Coil Current]

Parameter Number:

333,275,_,_,_.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-4-61

Group:

Diagnostics

Units:

Amperes

Minimum Value:

00.000A

Maximum Value:

99.999 A

Default Value:

00.000A

This parameter allows the user to view the real time operating Coil

Current for IB4. The current will be the Hold current for Electrically

Held contactors, only, because the Close/Trip coils for Mechanically

Latched contactors are only momentary currents and are not sustained

for extended time periods. See “Coil Currents” in Chapter 4 for a

more detailed description of this feature.


Contactor Coil Current for IB5
[IB 5 Contactor Coil Current]

Parameter Number:

334,_,_,_,_.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-5-61

Group:

Diagnostics

Units:

Amperes

Minimum Value:

00.000A

Maximum Value:

99.999A

Default Value:

00.000A

This parameter allows the user to view the real time operating Coil

Current for IB5. The current will be the Hold current for Electrically

Held contactors, only, because the Close/Trip coils for Mechanically

Latched contactors are only momentary currents and are not sustained

for extended time periods. See “Coil Currents” in Chapter 4 for a

more detailed description of this feature.