5-10

IntelliVAC Plus Basic Wiring

1503-UM054C-EN-P – June 2013

Table 5.D – Maximum TDUV Time (without Capacitor)

Control Voltage

Max. TDUV Time (secs)

400 A

800 A

110/120 V

0.2

0.2

220/240 V

1.0

1.0

If the undervoltage condition persists beyond the set delay time, the

contactor will be opened and an undervoltage fault or warning condition

will occur (see Line Undervoltage and Table 4.F in Chapter 4).

Table 5.E – Maximum TDUV Time (with Capacitor)

Control Voltage

Max. TDUV Time (sec)

Capacitor

400A

800A

110/120V

2.0

2.0

1650uF - 80158-779-51-R

220/240V

2.0

2.0

330uF - 80158-779-52-R

*

Refer to Table 3.A for recommended fuse sizing.

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

STOP

START

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

M-IV

15

16

CONTACTOR

STATUS

M

M-IV

M

CAPACITOR

Figure 5.8 – TDUV Control Circuit