Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 238

Advertising
background image

Parameters B-63

1503-UM054C-EN-P – June 2013

Drop Out Time Setting for IB2
[IB 2 Drop Out Time]

Parameter Number:

114,98,82,66,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-2-13

Group:

Configuration

Units:

Milliseconds

Minimum Value:

50

Maximum Value:

240

Default Value:

50

This parameter allows the user to view and set the Drop Out Time

setting for the IB2 module. The Drop Out Time is the time required

from the moment that an Open or Trip command is issued to the time

that the Contactor Auxiliary Status contact, on IB2, closes, to

indicate that the contactor has opened. See Contactor Drop Out

Time in Chapter 8 and Table 8.B.


Drop Out Time Setting for IB3
[IB 3 Drop Out Time]

Parameter Number:

115,99,83,_,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-3-13

Group:

Configuration

Units:

milliseconds

Minimum Value:

50

Maximum Value:

240

Default Value:

50

This parameter allows the user to view and set the Drop Out Time

setting for the IB3 module. The Drop Out Time is the time required

from the moment that an Open or Trip command is issued to the time

that the Contactor Auxiliary Status contact, on IB3, closes, to

indicate that the contactor has opened. See Contactor Drop Out

Time in Chapter 8 and Table 8.B.