8-8

Configuration/Programming

1503-UM054C-EN-P – June 2013

Programming the IntelliVAC Base Module

The IntelliVAC base module firmware is updated using the RS-485

terminal on either an IntelliVAC MC, or an IntelliVAC Plus board.

In order to perform a firmware update on the IntelliVAC Base

module you will require the following:

1. Either an MC or IE board

2. An RS-485 to RS-232 converter

3. RS-232 cable

4. A personal computer with a functional serial port.

Programming the IB using an IE Board

In order to flash firmware to the base module using the IntelliVAC

Plus module take the following steps.

Power down the unit.

Remove The RS-485 link that goes from the IE module to any

other MC modules, and connect this cable to the RS-485 to RS-232

converter per the following picture.


Figure 8.3 – Hardware Set-up for Flashing Firmware