Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 245

Advertising
background image

B-70

Parameters

1503-UM054C-EN-P – June 2013


Contactor Pick Up Time for IB5
[IB 5 Pick Up Time]
Parameter Number:

127,_,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-5-18

Group:

Configuration

Units:

mSeconds

Minimum Value:

0

Maximum Value:

255

Default Value:

0

This parameter allows the user to view the Pick Up Time for the IB5

contactor. The Pick Up Time is the interval from when a Close or

Trip command is issued to the time that the Contactor Auxiliary

contact on IB5 opens, indicating that the contactor is closed.


TDUV Time Setting from IB1 DIP Switches
[IB 1 TDUV Time DIP Setting]

Parameter Number:

128,109,90,71,51.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-1-58

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the Time Delay Undervoltage

Setting set from the IB1 DIP switches. The Time Delay

Undervoltage Setting is initially set by the IB1 DIP switches but can

be over-ridden by Parameter #133 after which time the original IB1

DIP switch settings will no longer be used. See TDUV in Chapter 8

and Table 8.E.

Table B.28 – TDUV Time Setting From IB1 DIP Switches

Value

Enum Text

Description

0

0.2 Sec

0.2 Sec TDUV setting from IB1 DIP switches

1

0.5 Sec

0.5 Sec TDUV setting from IB1 DIP switches

2

1.0 Sec

1.0 Sec TDUV setting from IB1 DIP switches

3

2.0 Sec

2.0 Sec TDUV setting from IB1 DIP switches