Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 209

Advertising
background image

B-34

Parameters

1503-UM054C-EN-P – June 2013

Enhanced Module Hardware Output State
[IE Hardware Outputs]

Parameter Number:

62,50,38,26,14.

Access rule:

Get/Set

Data Type:

BYTE

Object Mapping:

0x4-2-3

Group:

Control

Units:

-

Minimum Value:

-

Maximum Value:

-

Default Value:

None

This parameter allows the user to view, as well as to control, the state

of the two (2) hardware output relays. Each bit position of the

parameter defines the state of one of the hardware outputs. If the bit

for a particular output is ‘0’ then that relay output will be Off but if

the bit is a ‘1’ then that relay output will be On.

Table B.5 – Enhanced Module Hardware Output States

Bit

Enum Text

Description

0

Bit 0: DLX Output A

Status of DeviceLogix Output A

1

Bit 0: DLX Output B

Status of DeviceLogix Output B

2

Unused

3

Unused

4

Unused

5

Unused

6

Unused

7

Unused

The outputs can each be toggled On or Off as shown in the following

RSNetworx screen in Figure B.1.


Defines the Power Source for the IE Board
[Current Power Source]

Parameter Number:

63,51,39,27,15.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x3-1-102

Group:

Control

Units:

-

Minimum Value:

0 = Power from DeviceNet

Maximum Value:

1 = Power from IB

Default Value:

0

This parameter allows the user to determine the source of operating

power for the IE board. This power can either be obtained from the

IB board or from DeviceNet.