Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 231

Advertising
background image

B-56

Parameters

1503-UM054C-EN-P – June 2013

Time Delay UnderVoltage Setting for IB3
[IB 3 TDUV Configure]

Parameter Number:

100,87,74,_,_.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x384-3-15

Group:

Configuration

Units:

-

Minimum Value:

0 = Disable

Maximum Value:

1 = Enable

Default Value:

0

This parameter allows the user to view and set the status of the Time

Delay UnderVoltage setting for the IB3 contactor module. If it is

disabled then the TDUV feature for the IB3 contactor is disabled. If

it is enabled then the TDUV feature for the IB3 contactor is enabled.

See TDUV in Chapter 8 and Table 8.D.


Time Delay UnderVoltage Setting for IB4
[IB 4 TDUV Configure]

Parameter Number:

101,88,_,_,_.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x384-4-15

Group:

Configuration

Units:

-

Minimum Value:

0 = Disable

Maximum Value:

1 = Enable

Default Value:

0

This parameter allows the user to view and set the status of the Time

Delay UnderVoltage setting for the IB4 contactor module. If it is

disabled then the TDUV feature for the IB4 contactor is disabled. If

it is enabled then the TDUV feature for the IB4 contactor is enabled.

See TDUV in Chapter 8 and Table 8.D.