Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 189

B-14
Parameters
1503-UM054C-EN-P – June 2013
Trip Coil Command for IntelliVAC Base Unit #2
[IB 2 Trip Coil Command]
Parameter Number:
22,18,14,10,_.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0x384-2-5
Group:
Control
Units:
-
Minimum Value:
0 = Off
Maximum Value:
1 = On
Default Value:
0
This parameter allows the user to view as well as change the Trip
Coil command for the IntelliVAC Basic Module #2. An Off refers to
the Trip command not being present and not applying power to the
Trip coil. An On refers to the Trip command being present and
applying power to the Trip coil.
Trip Coil Command for IntelliVAC Base Unit #3
[IB 3 Trip Coil Command]
Parameter Number:
23,19,15,_,_.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0x384-3-5
Group:
Control
Units:
-
Minimum Value:
0 = Off
Maximum Value:
1 = On
Default Value:
0
This parameter allows the user to view as well as change the Trip
Coil command for the IntelliVAC Basic Module #3. An Off refers to
the Trip command not being present and not applying power to the
Trip coil. An On refers to the Trip command being present and
applying power to the Trip coil.