Net out 28/stop, Net out 29/fwd, Net out 30/rev – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 160: Net out 31/jog, Hardware set up for this example, Figure 9.19 – basic logic program

DeviceLogix 9-37
1503-UM054C-EN-P – June 2013
This is the output portion of the “Start” dual function bit.
Net Out 28/Stop
This is the output portion of the “Stop” dual function bit.
Net Out 29/FWD
This is the output portion of the “FWD” dual function bit.
Net Out 30/REV
This is the output portion of the “REV” dual function bit.
Net Out 31/Jog
This is the output portion of the “Jog” dual function bit.
Customized Logic
Simple example
Hardware set up for this example:
A Normally open pushbutton is connected to DLX Input 1
A Normally closed pushbutton is connected to DLX Input 2
An Electrically held contactor is connected to the IntelliVAC
Plus unit
Per Rockwell Standard a Normally closed contactor Auxiliary
contact is connected to IB1-Aux.
Figure 9.19 – Basic Logic Program