Pre configured logic mode, Figure 9.20 – select pre-configured logic program – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 161

Advertising
background image

9-38

DeviceLogix

1503-UM054C-EN-P – June 2013

This is an example of a basic logical replacement for a typical relay

control circuit. Pushing the start pushbutton will cause the DLX1

Input 1 to go to “1” which is then tied to the “Net out 27/Start”

output tag which is a dual function bit which controls the “Start”

input tag. When this goes to “1” the output gate of the “OR” gate

goes to “1” and assuming the Normally closed “STOP” pushbutton is

not depressed the output of the “AND” gate will got to “1” and close

the contactor. The auxiliary input of the contactor will then close

which will keep the “OR” gate at “1”. This means the contactor will

remain closed until the “STOP” pushbutton is depressed.

Pre configured Logic Mode

:

The IntelliVAC Plus comes with five preprogrammed logic programs

corresponding to the 5 most common types of Rockwell Automation

MV controllers requiring multi contactor control. The five

preconfigured logic blocks are:

RVAT (reduced voltage autotransformer starter)

RVR (reduced voltage reactor starter)

FVR (full voltage reversing starter)

SMC (“smart motor controller” solid-state reduced voltage starter)

SMC+ PFCC (“smart motor controller” with the addition of

power factor correcting capacitors)

These control profiles can be selected in the device parameters page

in RSNetworx. They are located in the Control parameter group.

Figure 9.20 – Select Pre-Configured Logic Program