Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 247

Advertising
background image

B-72

Parameters

1503-UM054C-EN-P – June 2013

Table B.30 – TDUV Time Setting From IB3 DIP Switches

Value

Enum Text

Description

0

0.2 Sec

0.2 Sec TDUV setting from IB3 DIP switches

1

0.5 Sec

0.5 Sec TDUV setting from IB3 DIP switches

2

1.0 Sec

1.0 Sec TDUV setting from IB3 DIP switches

3

2.0 Sec

2.0 Sec TDUV setting from IB3 DIP switches



TDUV Time Setting from IB4 DIP Switches
[IB 4 TDUV Time DIP Setting]

Parameter Number:

131,112,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-4-58

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the Time Delay Undervoltage

Setting set from the IB4 DIP switches. The Time Delay

Undervoltage Setting is initially set by the IB4 DIP switches but can

be over-ridden by Parameter #136 after which time the original IB4

DIP switch settings will no longer be used. See TDUV in Chapter 8

and Table 8.E.

Table B.31 – TDUV Time Setting From IB4 DIP Switches

Value

Enum Text

Description

0

0.2 Sec

0.2 Sec TDUV setting from IB4 DIP switches

1

0.5 Sec

0.5 Sec TDUV setting from IB4 DIP switches

2

1.0 Sec

1.0 Sec TDUV setting from IB4 DIP switches

3

2.0 Sec

2.0 Sec TDUV setting from IB4 DIP switches