Parameters B-169

1503-UM054C-EN-P – June 2013


Altitude Settings on MC Units Inconsistent
[MC Altitude Set Warning]

Parameter Number:

327,269,211,153,94.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0xB4-1-122

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Fault

Maximum Value:

1 = MC Altitude setting inconsistent

Default Value:

0

This parameter allows the user to view the status of the Altitude

settings from the various IntelliVAC MC units. If this bit is a ‘0’

then all MC units have the same altitude setting and no further action

is required. If this bit is a ‘1’ then not all of the MC units have the

same altitude setting.

Since all of the contactors in an IntelliVAC MC system will be

located at the same altitude, the altitude parameter should be the

same for each of the units. If all of the units are not set to the same

altitude, then there will definitely be a problem with the coil

operating currents of some of the units. See Table 8.A for setting the

altitude parameters for each of the IB units in an MC system.


Time Delay UnderVoltage Time Source
[TDUV Time Source]

Parameter Number:

328,270,212,154,95.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0xB4-1-123

Group:

Diagnostics

Units:

-

Minimum Value:

0 = From IB

Maximum Value:

1 = From IE

Default Value:

0

This parameter allows the user to view and set the status of the

TDUV Time Source. If this bit is a ‘0’ then the IB DIP switch

setting is used as the TDUV Time Source. If this bit is a ‘1’ then the

IE setting in DeviceLogix is used as the TDUV Time Source.