Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 69

Advertising
background image

4-42

Description of Features

1503-UM054C-EN-P – June 2013

Table 4.I – DeviceNet Module Status LED

Fault/Warning

Red LED

Green LED

Description

None

Off

Off

No power from IB or

DeviceNet

Warning

Off

Flashing

In standby – needs

commissioning

None

Off

Solid On

Normal operation

Warning

Flashing

Off

Recoverable fault or device

MAC switch address is

changed online

Fault

Solid On

Off

Unrecoverable fault

None

Flashing

Flashing

Device self testing

No Power from IB or DeviceNet

This is a Normal condition if there are no input power sources to the

IntelliVAC Plus module. If this condition exists and there is at least

one source of external power supplied to the IntelliVAC Plus unit

then a serious problem may exist. Refer all servicing to qualified

service personnel or see the trouble shooting section in Chapter 10.

The Advanced module has no power from either the Basic module or

from DeviceNet.

The causes of the loss of Basic module power are either that there is

no 120/240V mains input power to the IntelliVAC plus module or

that this input voltage is <50Vrms. Also, the internal DC power

source on the Basic module has failed or the internal DC power

source on the Advanced module has failed, or both. Also, there is no

DeviceNet power or the internal DC power source of the Advanced

module has failed.

The DeviceNet status LED is off.

In Standby – Needs Commissioning

This is a Warning condition and indicates that the IntelliVAC Plus

needs commissioning due to a missing, incomplete or incorrect

configuration.

The DeviceNet status LED is flashing Green.

Normal Operation

This is a Normal condition and indicates that the IntelliVAC Plus is

operating in a normal condition.