Troubleshooting 10-5

1503-UM054C-EN-P – June 2013

Table 10.B - IE Operations Troubleshooting Procedures (cont.)

Plus Status

LED Color

State

Condition/Possible Cause

Corrective Action

Green

2 pulses

Warning

RTC failure

RTC not responding

1. Replace the IntelliVAC Plus module.

Green

3 pulses

Warning

Line undervoltage

Input mains voltage is too low

Input mains voltage is too low on other

MC units

Check the mains input line and verify that it remains

greater than 95Vrms to allow a contactor to be

closed. If the input voltage remains less than 95Vrms

then improvements to the source must be made.

This warning can be from any of the IntelliVAC MC

units in an MC system. Perform the same checks for

those units as well.

Green

4 pulses

Warning

Line overvoltage

Input mains voltage is too high

Input mains voltage is too high on other

MC units

Check the mains input line and verify that it remains

lower than 265Vrms to prevent damage to the

IntelliVAC Plus module.

This warning can be from any of the IntelliVAC MC

units in an MC system. Perform the same checks for

those units as well.

Green

5 pulses

Warning

Extended close time

Faulty contactor mechanics

Faulty contactor coil

Faulty contactor coil on other MC units

Check the mechanical condition of the contactor as

this warning is an indication that the moving

mechanisms of the contactor are beginning to wear.

Check the resistance of the contactor coil and

compare it to the values.

This warning can be from any of the IntelliVAC MC

units in an MC system. Perform the same checks for

those units as well.

Green

6 pulses

Warning

DeviceNet power loss

1. DeviceNet connection faulty

2. DeviceNet input voltage too low

Check that the DeviceNet connections to the

IntelliVAC Plus are correct and that the DeviceNet

source connections are correct as well.

Check that the DeviceNet input voltage at terminals

TB1-5,1 is greater than the minimum voltage as

defined in the Electrical Specification

Green

7 pulses

Warning

MC Altitude setting

Incorrect altitude DIP switch setting

The altitude setting defined by the DIP switches

(SW1-1,2,3) on the Basic module is not consistently

set on all units in an MC system. Adjust the DIP

switches on all units to the same altitude setting.