Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 26

Advertising
background image

Installation 3-3

1503-UM054C-EN-P – June 2013

Figure 3.2 – Typical Mounting Configurations



Note:

Adjacent IntelliVAC modules may be mounted with a

minimum separation of 6.4 mm (0.25 inches).

Control with Solid-State Devices

If control devices that employ electronic or suppressed output

circuits are used in the rung(s) that control the inputs to the

IntelliVAC, alternate arrangements may be required. Devices

employing transistor or triac output circuits have finite impedance

and allow a leakage current to flow in the blocking or off state.

Some PLC and I/O modules with relay outputs also have R-C

snubber circuits across the contacts to suppress noise generated

during contact opening. The impedance of these circuits also allows

leakage current to flow when the contacts are open. The high

impedance input circuits of the IntelliVAC Plus have been designed

to minimize sensitivity to these leakage currents, however, they may

be triggered by excessive leakage current or residual terminal

voltage, causing unintended operation of the contactor, or

maintenance of the closed state when the control signal is removed.

Advertising