Max close time @ 120v, Max close time @ 240v – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 64

Advertising
background image

Description of Features 4-37

1503-UM054C-EN-P – June 2013

Table 4.G – Contactor Extended Close Times

CONTACTOR CONFIGURATION @ Vinput

Max Close Time

@ 120V

Max Close

Time @ 240V

400A Mech. Latch (7.2 kV)

150 ms

150 ms

400A Elec. Held (7.2 kV)

150 ms

150 ms

800A Mech. Latch (7.2 kV)

150 ms

150 ms

800A Elec. Held (7.2 kV)

150 ms

150 ms

The ‘Extended Close Time’ Warning is used to indicate that there is

a potential problem with one or more of the up to five contactors in

an MC system. The normal close time for a contactor should never

exceed 200 ms, however, if it exceeds the values in Table 4.G, then

this is an indication that there may be a potential problem with one or

more contactors. To perform this measurement the close time will

be averaged over the last 5 closures. A measurement of the actual

close time for each of the five contactors is available as a DeviceNet

parameter (see Appendix B). To indicate to the user which

contactor(s) have an ‘Extended Close Time’ problem the following

DeviceNet messaging should be displayed as follows:

‘IB1 Extended Pick Up Time =’ ‘Present’ or ‘Not Present’

‘IB2 Extended Pick Up Time =’ ‘Present’ or ‘Not Present’

‘IB3 Extended Pick Up Time =’ ‘Present’ or ‘Not Present’

‘IB4 Extended Pick Up Time =’ ‘Present’ or ‘Not Present’

‘IB5 Extended Pick Up Time =’ ‘Present’ or ‘Not Present’

These messages will indicate all of the contactors that have had an

Extended Close Time condition.

DeviceNet Power Loss

This is a Warning condition which indicates that the DeviceNet

power on connector P1 (pins 5,1) has decreased below 10VDC. For

this warning to be annunciated, the DeviceNet power must have been

good (i.e. >10VDC) before the loss of this power. If an IntelliVAC

Plus were to power up without any DeviceNet power then this

warning would not occur. DeviceNet power must have been

available at some point and then lost before this warning is

annunciated. Check the DeviceNet power source or the connections

on the P1 (pins 5.1) connector.

The IntelliVAC Plus status LED is pulsing Green with a pattern of 6

pulses.