Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 257

Advertising
background image

B-82

Parameters

1503-UM054C-EN-P – June 2013


Jog Time for IB3 [IB 3 Jog Time]

Parameter Number:

150,127,104,_,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-3-21

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

30

Default Value:

12

This parameter allows the user to view and set the Jog Time for

contactor IB3. It indicates the amount of time that a contactor can be

Jogged (momentarily closed) for. This is only for Electrically Held

contactors and makes use of the Open command. See Temporary

Jog Function in Chapter 4 for a more detailed description of this

feature.


Jog Time for IB4 [IB 4 Jog Time]

Parameter Number:

151,128,_,_,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-4-21

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

30

Default Value:

12

This parameter allows the user to view and set the Jog Time for

contactor IB4. It indicates the amount of time that a contactor can be

Jogged (momentarily closed) for. This is only for Electrically Held

contactors and makes use of the Open command. See Temporary

Jog Function in Chapter 4 for a more detailed description of this

feature.