Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 246

Advertising
background image

Parameters B-71

1503-UM054C-EN-P – June 2013


TDUV Time Setting from IB2 DIP Switches
[IB 2 TDUV Time DIP Setting]
Parameter Number:

129,110,91,72,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-2-58

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the Time Delay Undervoltage

Setting set from the IB2 DIP switches. The Time Delay

Undervoltage Setting is initially set by the IB2 DIP switches but can

be over-ridden by Parameter #134 after which time the original IB2

DIP switch settings will no longer be used. See TDUV in Chapter 8

and Table 8.E.

Table B.29 – TDUV Time Setting From IB2 DIP Switches

Value

Enum Text

Description

0

0.2 Sec

0.2 Sec TDUV setting from IB2 DIP switches

1

0.5 Sec

0.5 Sec TDUV setting from IB2 DIP switches

2

1.0 Sec

1.0 Sec TDUV setting from IB2 DIP switches

3

2.0 Sec

2.0 Sec TDUV setting from IB2 DIP switches


TDUV Time Setting from IB3 DIP Switches
[IB 3 TDUV Time DIP Setting]

Parameter Number:

130,111,92,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-3-58

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the Time Delay Undervoltage

Setting set from the IB3 DIP switches. The Time Delay

Undervoltage Setting is initially set by the IB3 DIP switches but can

be over-ridden by Parameter #135 after which time the original IB3

DIP switch settings will no longer be used. See TDUV in Chapter 8

and Table 8.E.