Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 341

B-166
Parameters
1503-UM054C-EN-P – June 2013
Length of Event Log on IB4
[IB 4 Event Present Length]
Parameter Number:
321,264,_,_,_.
Access rule:
Get
Data Type:
UINT
Object Mapping:
0x384-4-52
Group:
Diagnostics
Units:
-
Minimum Value:
0
Maximum Value:
100
Default Value:
0
This parameter allows the user to view the Length of the Event Log
for IB4. Up to a maximum of 100 Events can be stored, for IB4, in
the Event Log before older Events are overwritten with newer
Events. See Event Log in Chapter 4 for a more detailed description
of this feature.
Length of Event Log on IB5
[IB 5 Event Present Length]
Parameter Number:
322,_,_,_,_.
Access rule:
Get
Data Type:
UINT
Object Mapping:
0x384-5-52
Group:
Diagnostics
Units:
-
Minimum Value:
0
Maximum Value:
100
Default Value:
0
This parameter allows the user to view the Length of the Event Log
for IB5. Up to a maximum of 100 Events can be stored, for IB5, in
the Event Log before older Events are overwritten with newer
Events. See Event Log in Chapter 4 for a more detailed description
of this feature.