Parameters

1503-UM054C-EN-P – June 2013

Type of Contactor Selected for IB4 [IB 4 Contactor Type]

Parameter Number:

96,84,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-4-14

Group:

Configuration

Units:

-

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the status of the type of

contactor that is being controlled by the IB4 module. This value is

set by the DIP switches on the IB4 module only (see Table 8.C).

Table B.21 – Type of Contactor for IB4 Unit

Value

Enum Text

Description

0

400A Mech. Latch

IB4 is a 400A Mechanically Latched contactor

1

400A Elec. Held

IB4 is a 400A Electrically Held contactor

2

800A Mech. Latch

IB4 is an 800A Mechanically Latched contactor

3

800A Elec. Held

IB4 is an 800A Electrically Held contactor


Type of Contactor Selected for IB5 [IB 5 Contactor Type]

Parameter Number:

97,_,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-5-14

Group:

Configuration

Units:

-

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the status of the type of

contactor that is being controlled by the IB5 module. This value is

set by the DIP switches on the IB5 module only (see Table 8.C).

Table B.22 – Type of Contactor for IB5 Unit

Value

Enum Text

Description

0

400A Mech. Latch

IB5 is a 400A Mechanically Latched contactor

1

400A Elec. Held

IB5 is a 400A Electrically Held contactor

2

800A Mech. Latch

IB5 is an 800A Mechanically Latched contactor

3

800A Elec. Held

IB5 is an 800A Electrically Held contactor