Description of Features 4-29

1503-UM054C-EN-P – June 2013

Microcontroller Malfunction

This is a serious Fault condition and the IntelliVAC Plus will not

respond to other commands. Refer all servicing to a qualified

service personnel or see the trouble shooting section in Chapter 10.

This indicates that the Basic module within the IntelliVAC Plus unit

has a severe fault due to a microcontroller malfunction and the status

of the contactor being controlled is in an Open condition.

The Module status LED is solid red indicating a severe module fault

and the Module status relay is open to prevent externally connected

circuits from functioning.

The Contactor status LED is Red to indicate that the contactor is in

an Open condition and the Contactor status relay is Open to reflect

the status of the contactor thus preventing externally connected

circuits to function.

This condition is valid for both Electrically Held and Mechanically

Latched contactors.


Power Up with Invalid DIP Switch Configuration

This is a Fault condition and the IntelliVAC Plus will not respond to

other commands until this condition is restored to normal. Check the

settings of the DIP switches and make sure that they are set correctly.

This indicates that the Basic module within the IntelliVAC Plus unit

has a fault due to the module powering up with an invalid DIP switch

configuration and the status of the contactor being controlled is in an

Open condition.

The Module status LED is flashing Red followed by a pause, to

indicate a contactor module that has powered up with an invalid DIP

switch configuration and the Module status relay is open to prevent

externally connected circuits from functioning.

The Contactor status LED is off to indicate that the contactor is in an

Open condition and the Contactor status relay is Open to reflect the

status of the contactor thus preventing externally connected circuits

from functioning.

This condition is valid for both Electrically Held and Mechanically

Latched contactors.