Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 198

Parameters B-23
1503-UM054C-EN-P – June 2013
Close Coil Current for IntelliVAC Base Unit #5
[IB 5 Close Current]
Parameter Number:
40_,_,_,_.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-5-8
Group:
Control
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the average value for the
Close coil current on the IntelliVAC Basic Module #5. This coil
current is only valid for the first 200mS after the Close coil is
energized.
Hold Coil Current for IntelliVAC Base Unit #1
[IB 1 Hold Current]
Parameter Number:
41,33,25,17,9.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-1-9
Group:
Control
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the average value for the
Hold coil current on the IntelliVAC Basic Module #1. This coil
current is only valid after the first 200mS after the Close coil is
energized and the Close coil is in the Hold state.