Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 198

Advertising
background image

Parameters B-23

1503-UM054C-EN-P – June 2013


Close Coil Current for IntelliVAC Base Unit #5
[IB 5 Close Current]
Parameter Number:

40_,_,_,_.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-5-8

Group:

Control

Units:

Amperes

Minimum Value:

00.000A

Maximum Value:

99.999A

Default Value:

00.000A

This parameter allows the user to view the average value for the

Close coil current on the IntelliVAC Basic Module #5. This coil

current is only valid for the first 200mS after the Close coil is

energized.


Hold Coil Current for IntelliVAC Base Unit #1
[IB 1 Hold Current]

Parameter Number:

41,33,25,17,9.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-1-9

Group:

Control

Units:

Amperes

Minimum Value:

00.000A

Maximum Value:

99.999A

Default Value:

00.000A

This parameter allows the user to view the average value for the

Hold coil current on the IntelliVAC Basic Module #1. This coil

current is only valid after the first 200mS after the Close coil is

energized and the Close coil is in the Hold state.