Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 241

Advertising
background image

B-66

Parameters

1503-UM054C-EN-P – June 2013

Table B.24 – Drop Out Time Settings from IB2 DIP Switches

Value

Enum Text

Description

0

50 ms

50 ms from IB2 DIP switches

1

75 ms

75 ms from IB2 DIP switches

2

100 ms

100 ms from IB2 DIP switches

3

130 ms

130 ms from IB2 DIP switches

4

150 ms

150 ms from IB2 DIP switches

5

175 ms

175 ms from IB2 DIP switches

6

200 ms

200 ms from IB2 DIP switches

7

240 ms

240 ms from IB2 DIP switches

Note:

The drop off time would be 6mS longer if the close command

is applied on IB.



Drop Out Time Setting From IB3 DIP Switches
[IB 3 Drop Out Time DIP Setting]

Parameter Number:

120,103,86,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-3-49

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

7

Default Value:

0

This parameter allows the user to view the Drop Out Time Setting

set from the IB3 DIP switches. The Drop Out Time is initially set by

the IB3 DIP switches but can be over-ridden by Parameter #115 after

which time the original IB3 DIP switch settings will no longer be

used.

Table B.25 – Drop Out Time Settings From IB3 DIP Switches

Value

Enum Text

Description

0

50 ms

50 ms from IB3 DIP switches

1

75 ms

75 ms from IB3 DIP switches

2

100 ms

100 ms from IB3 DIP switches

3

130 ms

130 ms from IB3 DIP switches

4

150 ms

150 ms from IB3 DIP switches

5

175 ms

175 ms from IB3 DIP switches

6

200 ms

200 ms from IB3 DIP switches

7

240 ms

240 ms from IB3 DIP switches

Note:

The drop off time would be 6 ms longer if the close command

is applied on IB.