Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 356

Advertising
background image

Parameters B-181

1503-UM054C-EN-P – June 2013

Status Word for the MC System
[MC System Status]

Parameter Number:

346,285,224,163,101.

Access rule:

Get/Set

Data Type:

WORD

Object Mapping:

0xB4-1-127

Group:

Diagnostics

Units:

-

Minimum Value:

0

Maximum Value:

0xFFFF

Default Value:

0

This parameter allows the user to view the MC System Status Word.

If a bit is ‘0’ then the fault or warning is not present. If a bit is a ‘1’

then the fault or warning is present. See Table 4.H in Chapter 4 for a

detailed description of each of the MC System Status Word bits.

Table B.45 – Status Word for MC System

Bit

Enum Text

Description

0

Aggregate warning status

Aggregate warning status

1

Aggregate fault status

Aggregate fault status

2

IE warning status

IE warning status

3

IE fault status

IE fault status

4

IB5 warning status

IB5 warning status

5

IB5 fault status

IB5 fault status

6

IB4 warning status

IB4 warning status

7

IB4 fault status

IB4 fault status

8

IB3 warning status

IB3 warning status

9

IB3 fault status

IB3 fault status

10 IB2 warning status

IB2 warning status

11 IB2 fault status

IB2 fault status

12 IB1 warning status

IB1 warning status

13 IB1 fault status

IB1 fault status

14 System running status

System running status

15 System ready status

System ready status