Parameters B-175

1503-UM054C-EN-P – June 2013

Status Word for IB3 [IB 3 Status Word]

Parameter Number:

337,278,219,_,_.

Access rule:

Get

Data Type:

WORD

Object Mapping:

0x384-3-62

Group:

Diagnostics

Units:

-

Minimum Value:

0

Maximum Value:

0xFFFF

Default Value:

0

This parameter allows the user to view the IB3 Status Word.

If a bit

is ‘0’ then the fault or warning is not present. If a bit is a ‘1’ then the

fault or warning is present.

Table B.41 – Status Word for IB3

Bit

Enum Text

Description

0

Bit 0: unused

unused

1

Bit 1: unused

unused

2

Bit 2: unused

unused

3

Bit 3: Power Up with Contactors Closed

Power Up with Contactor Closed IB3

4

Bit 4: Open Coil Open

Trip Coil Open on IB3

5

Bit 5: Close Coil Open

Close Coil Open on IB3

6

Bit 6: Power Up with Invalid DIPs

Power Up with Invalid DIPs on IB3

7

Bit 7: MC Malfunction

MC Malfunction on IB3

8

Bit 8: Drop Out During Hold

Drop Out During Hold on IB3

9

Bit 9: Contactor Fails to Drop Out

Contactor Fails to Drop Out on IB3

10 Bit 10: Power Up with Close Command

Power Up with Close Command on IB3

11 Bit 11: Long Close Time

Long Close Time on IB3

12 Bit 12: Undervoltage with Close Command Present Undervoltage with Close Command Present on IB3
13 Bit 13: Long Drop Out Time

Long Drop Out Time on IB3

14 Bit 14: Mechanical Latch Trip Fail

Mechanical Latch Trip Fail on IB3

15 Bit 15: Invalid Command

Invalid Command on IB3