Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 253

Advertising
background image

B-78

Parameters

1503-UM054C-EN-P – June 2013


Delay Restart Time for IB5
[IB 5 Delay Restart Time]
Parameter Number:

142,_,_,_,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-5-19

Group:

Configuration

Units:

Seconds

Minimum Value:

6

Maximum Value:

3600

Default Value:

12

This parameter allows the user to view and set the Delay Restart

Time between successive Open/Trip and Close commands for

contactor IB5. This sets a maximum repetition time for the cycling

of the contactor. It can also be used to prevent rapid restating of the

motor. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.


Delay Restart Wait Time for IB1
[IB 1 Delay Restart Wait Time]
Parameter Number:

143,121,99,77,54.

Access rule:

Get

Data Type:

UINT

Object Mapping:

0x384-1-20

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

3600

Default Value:

0

This parameter allows the user to view the Delay Restart Wait Time

for IB1. It shows the time left, as a constantly updated real time,

after the contactor has closed, before it is permitted to close again.

This parameter works in conjunction with parameter #138 which

defines the minimum time allowed between successive closings of

contactor IB1. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.