Troubleshooting

1503-UM054C-EN-P – June 2013

Table 10.B - IE Operations Troubleshooting Procedures (cont.)

Plus Status

LED Color

State

Condition/Possible Cause

Corrective Action

Red

Fault

RESET mode or firmware crash

+5V logic rail is too low

Faulty Enhanced microcontroller

Firmware crash

A RESET condition has occurred due to the +5V logic

rail being less than +4.65V. Check that the input

mains voltage is within the operating range as

defined in the Electrical Specification

A RESET condition has occurred due to a faulty

microcontroller on the Enhanced module. Replace

the IntelliVAC Plus module.

A RESET condition has occurred due to a firmware

crash. This may be due to a high level of externally

generated EMI entering the wires connecting to the

IntelliVAC Plus module. Recycle the input power for

both the mains input as well as the DeviceNet power.

If there is no improvement then analyze the wiring to

the IntelliVAC Plus to determine if there is an unusual

amount of electrical noise present. If there is

excessive noise present, then rectify the situation. If

the unit still remains in RESET mode then replace the

IntelliVAC Plus module.

Red

2 pulses

Fault

POST failure – RAM

Excessive EMI

A failure of one or more of the internal microcontroller

RAM cells has been detected. This may be due to

externally generated EMI entering the wires

connecting to the IntelliVAC Plus module, corrupting

the RAM memory. This may be due to a high level of

externally generated EMI entering the wires

connecting to the IntelliVAC Plus module. Recycle

the input power for both the mains input as well as

the DeviceNet power. If there is no improvement

then analyze the wiring to the IntelliVAC Plus to

determine if there is an unusual amount of electrical

noise present. If there is excessive noise present,

then rectify the situation. If not and the RAM fault

persists then replace the IntelliVAC Plus module.

Faulty RAM memory

The internal microcontroller RAM has one or more

defective cells and the IntelliVAC Plus must be

replaced.

Red

5 pulses

Fault

Application programming error – CRC

RS485 cables faulty

Excessive EMI in vicinity

Incorrect program being Flashed

Incorrect communications parameters

1. Check that the RS485 cable connecting the

IntelliVAC Plus module and the PC is correct.

2. Check that there is not an unusual amount of EMI

being emitted from external sources.

3. Check that the program being flashed is correct.

4. Check that the communications parameters are

correct (i.e. baud rate, star/stop bits, parity, flow

control).

Red

6 pulses

Fault

RS485 Communications fault from IB1

Faulty interboard connector

External RS485 source connected

Faulty IntelliVAC Plus unit

Remove the IntelliVAC Plus front panel, remove the

three mounting screws and then remove the

Enhanced circuit card. Check that the 16-pin

interboard connector is properly mating and that there

is no dirt in the connector.
Remove the external RS485 communications source.

Replace the IntelliVAC Plus module.