Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 39

Advertising
background image

4-12

Description of Features

1503-UM054C-EN-P – June 2013

Open Coil Test

To check that there is a coil(s) connected to the IntelliVAC Plus unit

a test is performed to confirm that the coil current is greater than 200mA.

If the coil current measured is lower than this threshold then it can be

assumed that the particular Coil Under Test (CUT) is open.

If the coil is an open circuit then the IntelliVAC Plus Module Status

LED will annunciate the fault (see Table 4.F). This fault will indicate

an open coil for any of the up to five (5) contactors connected in an

MC system.

This open coil test will be performed on a regular basis only when

the contactor is not being commanded to be closed. It will be

performed for all of the up to five (5) contactors attached and will be

executed once every minute. When an open coil is found the event

will be logged to the Event Log table (see Event Log Table 4.D) and

the IntelliVAC Plus Module Status LED will be turned on. If one or

more open coils are detected and then at some point the coil(s) is no

longer found to be open, then the IntelliVAC Plus Module Status

LED will be turned off.

Below are the DeviceNet messages displayed when an open coil

condition is detected:

‘IB1 Main Coil Open’ = Present or Not Present

‘IB2 Main Coil Open’ = Present or Not Present

‘IB3 Main Coil Open’ = Present or Not Present

‘IB4 Main Coil Open’ = Present or Not Present

‘IB5 Main Coil Open’ = Present or Not Present

The following are for mechanically latched contactors only.

‘IB1Trip Coil Open’ = Present or Not Present

‘IB2 Trip Coil Open’ = Present or Not Present

‘IB3 Trip Coil Open’ = Present or Not Present

‘IB4 Trip Coil Open’ = Present or Not Present

‘IB5 Trip Coil Open’ = Present or Not Present

For the Electrically Held contactor, this test for the main coil can be

performed whenever the coil is not in the pick-up or closed mode.

For the Mechanically Latched contactor, the test for the main coil

can be performed whenever the coil is not in the close mode and for

the trip coil, whenever this coil in not being activated.