Wiring guidelines mechanical latch contactors – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 82

IntelliVAC Plus Basic Wiring 5-7
1503-UM054C-EN-P – June 2013
IntelliVAC control may be used for mechanical latch contactors.
A momentary control signal is needed to close the contactor, and a
second momentary control signal is needed to open the contactor.
The momentary open/close commands must be at least 50
milliseconds in duration.
Refer to Figure 5.6 for a typical mechanical latch control scheme.
Note:
1. A mechanical latch contactor may already be closed when power
is applied to the IntelliVAC control module.
2. It is permissible to apply an open command to the IntelliVAC
module as power is re-applied.
MOV
3
2
1
EC
-
+
4
TCO
12
11
AUX
CCO
5
6
L1
L2/N
G
+ -
CLOSE
OVERLOAD
CONTROL
POWER
FUSE
*
CONTROL POWER
M-IV
9
10
CLOSE
CC
M-IV
M
MOV
TC
M
+ -
M-IV
7
8
OPEN
OPEN
OVERLOAD
* Refer to Table 5.A for recommended fuse sizing.
Figure 5.6 – Mechanical Latch Contactor Control
Wiring Guidelines
Mechanical Latch
Contactors