Wiring guidelines mechanical latch contactors – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 82

Advertising
background image

IntelliVAC Plus Basic Wiring 5-7

1503-UM054C-EN-P – June 2013


IntelliVAC control may be used for mechanical latch contactors.

A momentary control signal is needed to close the contactor, and a

second momentary control signal is needed to open the contactor.

The momentary open/close commands must be at least 50

milliseconds in duration.

Refer to Figure 5.6 for a typical mechanical latch control scheme.

Note:

1. A mechanical latch contactor may already be closed when power

is applied to the IntelliVAC control module.

2. It is permissible to apply an open command to the IntelliVAC

module as power is re-applied.

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

CLOSE

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

CC

M-IV

M

MOV

TC

M

+ -

M-IV

7

8

OPEN

OPEN

OVERLOAD

* Refer to Table 5.A for recommended fuse sizing.

Figure 5.6 – Mechanical Latch Contactor Control

Wiring Guidelines

Mechanical Latch

Contactors