Correct Termination Resistor Installed in MC System
[Correct MC Termination Resistor]

Parameter Number:

340,280,220,160,99.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-1-63

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the MC

Termination Resistor installation. If this bit is ‘0’, then the correct

MC Termination Resistor is not installed in the MC system. If this

bit is ‘1’, then the correct MC Termination Resistor is installed in the

MC system. For the MC system to have the correct Termination

Resistor installed, only the last MC unit in the MC system must have

its resistor turned on.


Termination Resistor Installed in IB2
[IB2 Termination Resistor]

Parameter Number:

341,281,221,161,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-2-63

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the MC

Termination Resistor installation on IB2. If this bit is ‘0’, then the

MC Termination Resistor is not installed on the IB2 unit. If this bit

is ‘1’, then the MC Termination Resistor is installed on the IB2 unit.

For the MC system to have the correct Termination Resistor installed,

only the last MC unit in the MC system must have its resistor turned

on.