Table 10.C – IE Operational Trouble Shooting Procedures (cont.)

7-Segment

Display

State

Condition/Possible Cause

Corrective Action

1

flash

Fault

MC system bad MC #1

IntelliVAC MC #1 not communicating

Check the interboard connector between the Basic

and Enhanced modules in the IntelliVAC Plus

module. Also, check the RS485 communications

cable between other IntelliVAC MC units, if they are

in the system.

1

flash

Fault

Incorrect R

TERM

Selected

In an IntelliVAC MC system, an incorrect R

TERM

setting can

Cause communication errors which will generate this

fault. Set the R

TERM

resistor on only the last

IntelliVAC MC unit in an IntelliVAC MC system. In a

single unit IntelliVAC MC system, there is no need to

install an additional R

TERM

resistor as it is already

installed on the Enhanced module contained in the

IntelliVAC Plus unit.

2

flash

Fault

MC system bad MC #2

IntelliVAC MC #2 not communicating

Incorrect R

TERM

selected

1.Check the RS485 communications cable between

IntelliVAC MC unit #2 and other IntelliVAC MC units,

if they are in the system.

2.In an IntelliVAC MC system, an incorrect R

TERM

setting can cause communication errors which will

generate this fault. Set the R

TERM

resistor on only

the last IntelliVAC MC unit in an IntelliVAC MC

system

3

flash

Fault

MC system bad MC #3

IntelliVAC MC #3 not communicating

Incorrect R

TERM

selected

Check the RS485 communications cable between

IntelliVAC MC unit #3 and other IntelliVAC MC units,

if they are in the system.

In an IntelliVAC MC system, an incorrect R

TERM

setting can cause communication errors which will

generate this fault. Set the R

TERM

resistor on only

the last IntelliVAC MC unit in an IntelliVAC MC

system

4

flash

Fault

MC system bad MC #4

IntelliVAC MC #4 not communicating

Incorrect R

TERM

selected

Check the RS485 communications cable between

IntelliVAC MC unit #4 and other IntelliVAC MC units,

if they are in the system.

In an IntelliVAC MC system, an incorrect R

TERM

setting can cause communication errors which will

generate this fault. Set the R

TERM

resistor on only

the last IntelliVAC MC unit in an IntelliVAC MC

system

5

flash

Fault

MC system bad MC #5

IntelliVAC MC #5 not communicating

Incorrect R

TERM

selected

Check the RS485 communications cable between

IntelliVAC MC unit #5 and other IntelliVAC MC units,

if they are in the system.

In an IntelliVAC MC system, an incorrect R

TERM

setting can cause communication errors which will

generate this fault. Set the R

TERM

resistor on only

the last IntelliVAC MC unit in an IntelliVAC MC

system