Wcc3.exe screen descriptions, Analog input screen, Wcc iii technical guide 3-32 – WattMaster WM-WCC3-TGD-01B User Manual

Page 146

Advertising
background image

WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-32

V

OUT

GND

+V

ATI

1 TO 8

1 TO 8

NO

LOAD
RESISTOR

Input Jumper must be set to THERM
There are berg jumpers that are under the SAT III cover that must be set.
JOX corresponds to X = 1 to 8 for the Analog Input jumper.
Example:
JO1 is for Analog Input #1
JO8 is for Analog Input #8

An Input Load Resistor must not be used as a pull down resistor, because
the required 5 volts comes from the Thermistor pull up resistor.
RX corresponds to X = 1 to 8 for the Analog Input load resistor.
Example as follows:
R1 is for Analog Input #1 R4 is for Analog Input #4
R6 is for Analog Input #6 R8 is for Analog Input #8

Testing with a voltmeter:
Measure from ATI to GND. You should get a voltage measurement that
corresponds to the ON / OFF. 5.0 Volts DC equals OFF
The V-Out output is not used for this application.

JOX

THERM
0-10V
0-5V
0-1V

CONNECTIONS ON

SAT III CONTROLLER

ANALOG INPUT AS AN ANALOG SWITCH INPUT - Thermistor Scaling Factor

0-1V INPUT

ANALOG INPUT SCALING - From Sat Analog Input Screen

Description:

Type: Analog General

Pattern for values associated with this input: xxx.x

Units @ 0 % Scale 0.0 Deg F Units of measure message #: 1

@ full scale: 100.0 Deg F Filter time constant: 0 Seconds

===========Binary Setpoint ===========

OFF above 80.0 Deg F On Message #: ON

ON below 50.0 Deg F Off Message #: OFF

SWITCH

BY OTHERS

V

OUT

GND

ATI

1 TO 8

NO
LOAD
RESISTOR

Input Jumper must be set to THERM
There are berg jumpers that are under the SAT III cover that must be set.
JOX corresponds to X = 1 to 8 for the Analog Input jumper.
Example:
JO1 is for Analog Input #1
JO8 is for Analog Input #8

An Input Load Resistor must not be used as a pull down resistor, because
the required 5 volts comes from the Thermistor pull up resistor.
RX corresponds to X = 1 to 8 for the Analog Input load resistor.
Example as follows:
R1 is for Analog Input #1 R4 is for Analog Input #4
R6 is for Analog Input #6 R8 is for Analog Input #8

Testing with a voltmeter:
Measure from ATI to GND. You should get a voltage measurement that
corresponds to the ON / OFF. 5.0 Volts DC equals OFF
The V-Out output is not used for this application.

JOX

THERM
0-10V
0-5V
0-1V

CONNECTIONS ON

SAT III CONTROLLER

ANALOG INPUT AS AN ANALOG SWITCH INPUT - Thermistor Scaling Factor

0-5V INPUT

ANALOG INPUT SCALING - From Sat Analog Input Screen

Description:

Type: Analog General

Pattern for values associated with this input: xxx.x

Units @ 0 % Scale 0.0 Deg F Units of measure message #: 1

@ full scale: 500.0 Deg F Filter time constant: 0 Seconds

===========Binary Setpoint ===========

OFF above 400.0 Deg F On Message #: ON

ON below 100.0 Deg F Off Message #: OFF

+V

1 TO 8

SWITCH

BY OTHERS

Analog Input Screen

Advertising