WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-60

Description: _____________

A short message is entered here which will be displayed on Summary
and Data Entry/Editing Screens to aid you in remembering points
within the system. You may enter up to ten characters (control
codes, ALT codes, and the double quote character are not allowed).

Contact Open Message #: ____

Contact Closed Message #: ____

Specifi es a pair of message numbers, the fi rst for the contact open
state and the second for the contact closed state. These numbers
refer to a message on the On/Off Message Screen. For example,
message #1 might be “Fan On” and message #2 “Fan Off.” If
you want the message on the Control Output Summary Screen to
be “Fan On” when the satellite contact is closed, enter “#1” as the
contact closed message etc.

Minimum Off Time:

_____ seconds

Minimum On Time:

_____ seconds

Specifi es the minimum ON and OFF times for switching a load
to its opposite state (i.e., ON to OFF or OFF to ON). That is, once
the satellite contact closes it will remain closed for the minimum
ON time, and once it opens it will remain open for the minimum
OFF time. The range is 0 to 60 seconds or minutes, depending on
the unit of time selected. Because this is a “choice” fi eld, the list
of available choices will be displayed at the bottom of the screen:

<Seconds, Minutes>

Make your selection by pressing the

<space bar>

once for each

choice, and when the desired unit of time appears, press the

<Enter>

key.

Note that the minimum ON and OFF time has precedence over
demand limiting, overrides, etc.

Contact is:

_________in “On” Schedule Selected by:________

_________in Primary Alt Mode Selected by:________

_________in Secondary Alt Mode Selected by:________

_________in Local Set Selected by:________

The fi rst fi eld specifi es whether the satellite contact is to Open or
Close when the binary value entered in its Selected by fi eld goes
On.

The Primary Alt mode has highest priority, followed by Secondary
Alternate
, and then On Schedule.

Since the fi rst fi eld is a “choice” fi eld, the list of available choices
will be displayed at the bottom of the screen:

<OPEN, CLOSED>

On the “On” schedule

< OPEN, CLOSED, HOLD LAST >

On the Primary Alt Mode, Secondary Alt Mode, and Local Set

Make your selection by pressing the

<space bar>

once for each

choice until the desired contact state has been selected, and then
press

<Enter>

.

Note that the

HOLD LAST

is available for Primary Alt,

Secondary Alt and Local Set modes only. If

HOLD LAST

is

selected in the Local Set mode, the contact will stay closed if
it was closed at the time the satellite went into local set or will
stay open if it was open when the satellite went into local set.

Control Output Time Clock Screen