Wcc3.exe screen descriptions, Dual limit screen, Control output dual limit screen – WattMaster WM-WCC3-TGD-01B User Manual

Page 170

Advertising
background image

WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-56

Satellite #: _____

Specifi es the number of the satellite you are currently editing. If
you would like to edit a different satellite, use the arrow keys to
move the cursor to this fi eld, enter the desired satellite number,
and press

<Enter>

.

Control Output _____

This fi eld actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:

<ANALOG INPUT, CONTROL OUTPUT, ANALOG OUTPUT,

TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT>

You may make your selection by pressing the

<space bar>

once

for each choice, until the desired point type has been selected. (If
you select a point type that is different than that currently being
displayed, the screen will be rewritten with the appropriate screen
and data.) The second fi eld specifi es the point number to edit. For
the Control Output Screen, this number can range from one to
eight. If you would like to edit a different point, simply position

the cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired point number, and press

<Enter>

.

Mode: ____________

Specifi es the mode type of the output contact. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:

<Undefi ned, EA Driver, Time Clock, Dual Limit>

You may make your selection by pressing the

<space bar>

once

for each choice, until the desired point type has been selected, and
then pressing

<Enter>

. (If you select a mode type that is different

than that currently being displayed, the screen will be rewritten
with the appropriate screen information.)

_______ Contact

Specifi es which of the two available contacts per point (H or C)
to confi gure. Because this is a “choice” fi eld, the list of available
choices will be displayed at the bottom of the screen:

<H,C>

Satellite # 1

CONTROL OUTPUT 1

Mode: Dual Limit

“H” Contact

Description: S1-K1h

Contact Open Message #: 2 Off

Analog Control by: ////

Contact Closed Message #: 1 On

Schedule Control by: 1

Minimum Off Time: 0 Seconds

Alternate Mode selected by: ////

Minimum On Time: 0 Seconds

Override OPEN when 0B2 is OFF

Hysteresis: +/- 0 x 1 DEG.

Low

Limit

Hi

Limit

Local

Set:

OPEN

Between

0

&

0

DEG.

On

Schedule:

OPEN

Between

0

&

0

DEG.

Off Schedule:

OPEN

Between

0

&

0 DEG.

On Schedule: (alt)

OPEN

Between

0

&

0 DEG.

Off Schedule:(alt)

OPEN

Between

0

&

0 DEG.

Data Register is measured from Midpoint and Refl ects Hysteresis

HOME for menu

DUAL LIMIT SCREEN

Control Output Screen’s WCC III Logical Address is XXXKYh or c, where XXX = Satellite Address #, K = Control Output,

Y = Control Output #, h = Heat (General Purpose), and c = Cool (General Purpose)

Control Output Dual Limit Screen