WCC III Technical Guide

12-26

12. WCC III INSTALLATION

If you want to test the ramp speed, disconnect all wires from the
“HEAT,” “COM1,” “COOL,” and “COM2” terminals and use a
volt meter to measure the DC voltage between “ANALOG OUT”
and “GND” as you jumper test point #4 (TP #4) to ground.

The voltage should increase from the minimum to the maximum
voltage during the set time interval. Then, remove the jumper from
“TP #4” and jumper “TP #5” to “GND.” The voltage between the
“ANALOG OUT” and “GND” terminals should decrease from the
maximum to the minimum voltage during the set time interval.

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

24VAC

120VAC

120VAC WIRING

BY OTHERS

TO OTHER
SAT III OR TO
WCC III - MCD

24V

AC

GND

TO OTHER

SAT III OR TO

WCC III - MCD
WIRE "T" TO "T"

"R" TO "R"
"SHD" TO "SHD"

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE ECCII
ANALOG OUTPUT BOARD - GROUND
CONNECTIONS MUST BE THE SAME.

ECC II ANALOG OUTPUT BOARD

Figure 12-22: ECC II Analog Output typical wiring connections to a SAT III controller