I. INTRODUCTION

WCC III Technical Guide

I-7

1 HSS communications port that can connect and
power up as many as 5 HSS expansion type boards.

16 additional optional Binary Inputs by using two
HSS port connected WCC III Binary Input with
Time Delay board.

16 additional optional Binary Relay Outputs by
using two HSS port connected WCC III Vout
RELAY boards (Relay N.O. Contacts)

The SAT III controller has 24 LEDs on the cover of the SAT III
controller. (Figure I-4)

The top 8 Status LED functions are as follows:

SAT REC

- This LED will be lit when communications

are being received by the SAT III Communications
Loop.

SAT XMIT

- This LED will be lit when communications

are being transmitted by the SAT III Communications
Loop.

HSS REC

- This LED will be lit when communications

are being received from the HSS port.

HSS XMIT

- This LED will be lit when communications

are being transmitted to the HSS port.

LOCAL SET

- This LED will be lit when

communications with the WCC III - MCD has not
occurred in at least the last two minutes. This means
that the SAT III is not communicating on the SAT III
communications loop. Setpoint control in the SAT III is
dependent on the LOCAL SET parameters and as such
is to be programmed into each control point by the user.

STATUS 1

- This LED blinks for every 1 second if SAT

III is alive.

STATUS 2

- This LED blinks for every 1 second during

power on delay, and then blinks every 8 seconds when
watchdog is enabled.

STATUS 3

- This LED blinks for every internal

calculation loop completion.

The lower 16 LEDs display the status of the 16 Relay Outputs. The
LEDs display the status of the eight “H” eight “C” contacts.

Figure I-4: SAT III Controller LEDs

Satellite Types - SAT III