16. WCC III V-OUT RELAY BOARD INSTALLATION

WCC III Technical Guide

16-6

OE430-02 Installation

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3 4

2

1

3 4

5 6 7 8

5 6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX

0-15VDC
OUTPUT

MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY

TO HSS EXPANSION BOARDS.
UP TO TWO WCC3 BINARY INPUT W/TIME DELAY
BOARDS, AND UP TO THREE V-OUT RELAY BOARDS
MAY BE CONNECTED TO A SAT III CONTROLLER
HSS COMMUNICATIONS PORT.

SAT III CONTROLLER

24VAC

24

V

A

C

GND

GROUND

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE WCC3
V-OUT RELAY BOARD - GROUND
CONNECTIONS MUST BE THE SAME.
USING THIS METHOD CAN NOT
DAMAGE EITHER DEVICES.

TO OTHER
SAT III OR TO
WCC III - MCD

24VAC

120VAC

TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3 4

2

1

3 4

5 6 7 8

5 6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX

0-15VDC
OUTPUT

MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY

24VAC

24

V

A

C

GND

GROUND

SAT III CONTROLLER

TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"

TO OTHER
SAT III OR TO
WCC III - MCD

24VAC

120VAC

"SAT 2 TYPE" V-OUT BOARD

A CHIPSWITCH MUST BE
PRESENT FOR EACH
OUTPUT TO FUNCTION

120VAC WIRING IS BY OTHERS

THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC3 BINARY INPUT BOARD IS 5 VA.
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O. BOARD IS 10 VA.(OE430-01)
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O./N.C. BOARD IS 20 VA. (OE430-02)

DAISY CHAIN OUT TO
OTHER WCC3 V-OUT RELAY
BOARD OR TO OTHER WCC3
BINARY INPUT W/TIME
DELAY BOARDS THAT ARE
TO BE CONNECTED TO THE
SAT III HSS
COMMUNICATIONS PORT.

CONNECTION FROM A SAT III CONTROLLER TO WCC3 V-OUT RELAY BOARD USING THE "NEW" HSS CABLE CONNECTION METHOD

120VAC WIRING IS BY OTHERS

THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC2 V-OUT RELAY BOARD IS 10 VA.
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O. BOARD IS 10 VA.(OE430-01)
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O./N.C. BOARD IS 20 VA. (OE430-02)

CONNECTIONS # 1 THRU # 8 TO THE OLD SAT II TYPE V-OUT BOARD INPUTS VIN 1 THRU VIN 8 CONNECTION METHOD.

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE "OLD"
SAT II TYPE V-OUT BOARD.
THE GROUND CONNECTIONS MUST BE
THE SAME. DAMAGE TO THE SAT III
CONTROLLER OR TO THE "OLD" SAT II
TYPE V-OUT BOARD CAN RESULT IN
VOIDING WARRANTY.

DUPLICATING THE ORIGINAL SAT II
V-OUT TYPE CONNECTION.
CONNECT ALL EIGHT OF THE SAT III
ANALOG OUTPUTS V-OUT #1 THRU
V-OUT # 8 TO THE "OLD" SAT II TYPE
V-OUT BOARD INPUTS # 1 THRU # 8.
CONNECT ONE OF THE SAT III GND
CONNECTIONS TO THE "OLD" SAT II
TYPE V-OUT BOARD GND
CONNECTION IF POSSIBLE.

TO HSS EXPANSION BOARDS.
UP TO TWO WCC3 BINARY INPUT W/TIME DELAY
BOARDS, AND UP TO THREE V-OUT RELAY BOARDS
MAY BE CONNECTED TO A SAT III CONTROLLER
HSS COMMUNICATIONS PORT.

SAT III CONTROLLER CONNECTION FOR A

BINARY OUTPUT TYPE CONNECTION.

WCC3 V-OUT RELAY
N.O./N.C. CONTACTS
(OE430-02)

CONNECTION FROM A SAT III CONTROLLER TO AN OLD SAT II TYPE V-OUT BOARD USING THE “OLD” HARD WIRED WAY. WIRING THE SAT III CONTROLLER’S V-OUT