The system architecture for the WCC III system interfacing with
the TUC/RTU controllers through the SAT 3C is shown below:

The SAT3C - General Information

(SS5004)

The SAT3C Controller has 8 status lights. The functions of these
LEDs are listed below.

SAT REC - This LED will be lit when communications are being
received by the SAT 3C Controller.

SAT XMIT - This LED will be lit when communications are being
transmitted by the SAT 3C Controller.

TUC REC - This LED will be lit when communications are being
received from the TUC/RTU RS-485 Communications Loop.

TUC XMIT - This LED will be lit when communications are being
transmitted to the TUC/RTU RS-485 Communications Loop.

LOCAL SET - This LED will be lit when no communications with
the WCC III-MCD has occurred in at least the last 2 minutes. This
means that this SAT 3C communications loop is not communicating
with the WCC III-MCD. All standalone setpoint control is
dependent on the LOCAL SET parameters that are programmed
into the SAT 3C controller by the user.

STATUS - This LED blinks for every second if SAT 3C is alive.

“C” MODE - This LED will be lit if this Controller is programmed
as a SAT 3C and blinks for every internal calculation loop
completion.

“D” MODE - This LED blinks for every second during power on
delay and blinks every 8 seconds when watchdog is enabled.

SAT ADDRESS DIPSWITCH - There are two dipswitches on
the cover of the SAT 3C controller, one dipswitch sets the address
of the SAT 3C controller. The other dipswitch sets various local
control options.