Zone controller actuator package wiring, Installation & wiring, Wiring considerations – WattMaster WM-WCC3-TGD-01B User Manual

Page 814: Override alarm

Advertising
background image

Zone Controller Actuator Package Wiring

1

0

OE282

24 VAC Transformer. Size As

Required For Number Of Controllers

Connected. Each VAV/Zone Controller

Actuator Package Requires 6 VA

Minimum.

Wire To Next VAV/Zone Controller Actuator

Package Or Device On The Local

Communications Loop Using 2 Conductor

Twisted Pair With Shield Cable Available From

WattMaster. All Communication Cable Used

Must Be Belden 82760 Or Its Equivalent.

Line

Voltage

24 VAC

Connector Not

Used With This

Product

Damper Actuator

Damper Actuator Cable

OE210-02, OE211-02, OE212-02

Or OE213-02 Modular Room Sensor

Display

Override

OVERRIDE

ALARM

Note: When Used, The CO Sensor Always Connects To The VAV/Zone

Controller First Using A TSDRSC Cable Of The Appropriate Length. The

Digital Room Sensor Then Connects To The CO Sensor With Another

TSDRSC Cable. The Total Length Of Both Cables Combined Cannot Exceed

120 Feet. If Using Only The Digital Room Sensor Use TSDRSC Cable To

Connect To The VAV/Zone Controller.

2

2

OE217-00

Digital Room Sensor

OE255-01 Or OE256-01

CO Sensor

2

Wiring When Using A Modular Sensor

Wiring When Using A Digital Room Sensor

OE255-01 Or OE256-01

CO Sensor

2

OE325-01 Fan & Reheat Expansion

Module

Connect FRP Tubing (By Others) To Terminal Unit Air

Flow Pickup Tube Hi & Lo Ports

This Expansion Module Is Only Required For Single Duct

Terminal Units With Reheat And All Fan Terminal Units

Modular Expansion Cable

Supplied With OE325-01 Expansion Module

FMRSC Cable

TSDRSC Cable

TSDRSC or FMRSC Cable As

Required. Select Cable

Depending On Sensor(s) Used.

See Notes Above For Details.

Optional - Discharge/Duct Air

Temperature Sensor. Locate

In Ductwork Downstream Of

The Terminal Unit.

Note: When Used, The CO2 Sensor Always Connects To The VAV/Zone

Controller First Using An TSDRSC Cable Of The Appropriate Length. The

Modular Room Sensor Then Connects To The CO2 Sensor With A FMRSC

Cable. The Total Length Of Both Cables Combined Cannot Exceed 120 Feet. If

Using Only The Modular Room Sensor, Use FMRSC Cable To Connect To The

VAV/Zone Controller.

ZONE

EXPA

NSION

YS
10

22

52
R

E

V

1

WATMASTER

CONTRO

LS
INC.

M

A

DE
IN

USA

Rc

R1

R2

R3

R4

AO
U

T

GND

RELAYS

ANALOG

OUTP

U

T

STAT

THERM
4-20mA

0-10V

0-5V

GND

AI

N

ANALOG

INPUT

VREF

EXPANSION IN

PWR

P

IC18
F4520

10A250V

A

C

~

5A

30VD

C

SA

VDE

G5Q-1A4

OMRON

DC24V

CH

IN

A

10A250V

A

C

~

5A

30VD

C

SA

VDE

G5Q-1A4

OMRON

DC24V

CH

IN

A

10A250V

A

C

~

5A

30VD

C

SA

VDE

G5Q-1A4

OMRON

DC24V

CH

IN

A

10A250V

A

C

~

5A

30VD

C

SA

VDE

G5Q-1A4

OMRON

DC24V

CH

IN

A

COMM

TB3

STAT

GND

GND

24VAC

24VAC

R

SHLD

T

TB2

REC

T
SHLD
R

24 VAC
GND

www.orioncontrols.com

OE744-32-VAVZ

P.I. VAV/ZONE

CONTROLLER ACTUATOR

PACKAGE

WattMaster

Label

WARNING: When Multiple

VAV/Zone Controller Actuator

Packages Are Powered From

A Single Transformer Polarity

Must Be Observed Or Damage

To The Controllers Will Result.

Figure 7: VAV/Zone Controller Actuator Package Wiring

Wiring Considerations

The OE325-01 Zone Controller Expansion Module connects to the
VAV/Zone Controller Actuator Package by means of a modular cable
provided with the expansion module. Power is supplied to the Zone
Controller Expansion Module by means of this modular cable. Screw
terminals are provided for connection of fi eld wiring to the relay and
analog outputs. The Expansion Module is used to supply extra relays
and/or analog outputs to control fan and heating functions for the VAV/
Zone Controller Actuator Package.

The OE325-01 Zone Controller Expansion Module is always shipped
loose for fi eld mounting by others. Be careful not to damage the elec-
tronic components when mounting the controller. Remove the controller
from its snap track mount. Mark the control enclosure base using the snap
track as a template. Drill pilot holes in the enclosure base and secure the

snap track to it using sheet metal screws. Do not allow metal shavings to
fall onto the circuit board. Re-attach the controller to the snap track. Be
sure the mounting location is close enough to the VAV/Zone Controller
Actuator Package so that the supplied modular cable will reach from it
to the Zone Controller Expansion Module.

Warning: The 4 relay outputs available on the OE325-01

Expansion Module are each rated for 1 Amp. @ 24

VAC. If your device load exceeds these limits, a

pilot duty relay (by others) must be used in the

circuit.

The wiring consideration information previously outlined for the VAV/
Zone Controller Actuator Package should be followed when wiring the
OE325-01 Zone Controller Expansion Module.

10

VAV/Zone Controller Actuator Package Technical Guide

Installation & Wiring

Advertising
This manual is related to the following products: