Scuscr.exe screens, Single duct globals and mode of operation screens, Wcc iii technical guide 4-36 – WattMaster WM-WCC3-TGD-01B User Manual

Page 346

Advertising
background image

WCC III Technical Guide

4-36

4. SCUSCR.EXE SCREENS

Figure 4-9: Single Duct Cooling Only - Pressure Dependent Mode of Operation Screen

SINGLE DUCT COOLING ONLY VAV BOX

{ TUC-2R }

Satellite: _ 4

Unit:

1

Location:

Version: 2.03

Analog Address Locations

Logic Switch Definitions

A1 - Space Temperature

L1

- Pushbutton Override Status

R1A - Cooling Demand

P1 - Damper Position

VAV BOX MODE OF OPERATION SELECTION

Enter Type of

Box Desired....................................:

0

0 = Single Duct Cooling Only Box

[ Pressure

Dependent ]

1 = Single Duct Cooling Only Box

[ Pressure Independent ]

2 = Parallel Fan Box w/Reheat

[ Pressure

Dependent ]

3 = Parallel Fan Box w/Reheat

[ Pressure Independent ]

4 = Series Fan Box w/Reheat

[ Pressure

Dependent ]

5 = Series Fan Box w/Reheat

[ Pressure Independent ]

6 = Heating/Cooling Changeover

[ Pressure

Dependent ]

7 = Heating/Cooling Changeover

[ Pressure Independent ]

8 = Single Duct Cooling w/Reheat

[ Pressure

Dependent ]

9 = Single Duct Cooling w/Reheat

[ Pressure Independent ]

NOTE:

You must have an Airflow Sensor for Pressure Independent Boxes!

Press < HOME > for Main Menu
Press < Ctrl- Right Arrow > for Status Screen

Single Duct Globals and Mode of Operation Screens

Advertising
This manual is related to the following products: