Sat iii controller, Wcc iii installation guide, Wcc iii technical guide 12-31 – WattMaster WM-WCC3-TGD-01B User Manual

Page 527: Sat iii, Pin #1, Sat iii hss port

Advertising
background image

12. WCC III INSTALLATION

GUIDE

WCC III Technical Guide

12-31

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32
16

64

L4
L3
L2

L1

L6
L5

L7

L11

L12

ON OFF

L10
L9

ON OFF

L15

L16

L14
L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3
OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

CH

I

10

A

2

50

V

A

C

~

5A

30

V

D

C

SA

VD

E

G5

Q-1

A

4

OM

R

O

N

DC2

4

V

CH

IN

A

C~

DC

SA

VD

E

N

WCC3 BINARY IN W/ TIME DELAY

WATTMASTER CONTROLS, INC

YS102072 REV 2

24VAC

120VAC

TO OTHER
SAT III OR TO
WCC III - MCD

CONNECTION FROM A SAT III CONTROLLER TO WCC3 BINARY INPUT W/TIME DELAY BOARD USING THE "NEW" HSS CABLE CONNECTION METHOD,
BUT USING THE HSS CABLE AS A POWER ONLY CONNECTION TO THE WCC3 BINARY INPUT W/TIME DELAY BOARD AND IGNORING THE HSS
COMMUNCATIONS TO AND FROM THE SAT III CONTROLLER.

HSS CABLE - ORDER STANDARD LENGTHS OF 1 FOOT, 1.5 FOOT, 3 FEET, 25 FEET, 40 FEET, 80 FEET, 120 FEET MAX

DRY INPUT CONTACTS ONLY
CONTACT CLOSURE TO GROUND
ONLY. NO 24VAC INPUTS

24
V

A

C

GN

D

TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"

"R" TO "R"
"SHD" TO "SHD"

BINARY INPUT BOARD GETS POWER ONLY FROM THIS HSS CABLE. COMMUNICATIONS ARE IGNORED

SEE FRONT PAGE FOR

DIP SWITCH SETTINGS

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE
BINARY INPUT BOARD - GROUND
CONNECTIONS MUST BE THE SAME.

SAT III CONTROLLER

PIN #1

ST

R

IP

E

IS

PIN

#1

SAT III
HSS PORT

120VAC WIRING IS BY OTHERS

THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC3 BINARY INPUT BOARD IS 5 VA.

UP TO TWO WCC3 BINARY INPUT W/TIME
DELAY BOARDS MAY BE WIRED TO THE

SAT III CONTROLLER USING THIS

METHOD. CONNECT THE FIRST WCC3
BINARY INPUT W/TIME DELAY BOARD
TO THE SAT III CONTROLLER COVER
MOUNTED L1 TO L8 DIP SWITCH BINARY
INPUTS, AND THE SECOND WCC3
BINARY INPUT W/TIME DELAY BOARD
TO THE SAT III CONTROLLERS COVER
MOUNTED L9 TO L16 DIP SWITCH
BINARY INPUTS.

REPLACE THE DIP SWITCH IN THE

SAT III CONTROLLERS COVER WITH

THE SUPPLIED RIBBON CABLE.
OBSERVE POLARITY OF PIN # 1
CONNECT PIN 1 TO PIN 1 AS SHOWN

Figure 12-26: The WCC III Binary Input with Time Delay board typical wiring diagram - Old wiring connection

method along with the with the HSS cable method to get power from the SAT III controller

WCC III Binary Input with Time Delay Board Old Wiring Method

Advertising