11. WCC III ALARMING

Port Number

The WCC3.exe program opens a two-way, secure communications
port that then allows for communication between WCC III – MCD
and the WCC3.exe program that is running on the WCC III front
end computer. This IP Address connection is done on a higher
address port number than normal (WCC III connection is port
number 39289) to help reduce the risk of computer hacking.

Port Number 25 should always be used on the WCC3 system,
but in rare instances other port addresses can be used to improve
security on the WCC III – MCD. This generally requires advanced
IT support for implementation.

Port Number “25” is the usual TCP port for common SMTP
operation.

Reply E-mail Address:

Some E-mail SMTP servers require a reply E-mail address during
the Authentication process.

The End User on the WCC3 system with internet access should
have an E-mail address that usually is provided with the static
internet address or static Host name that comes from the internet
service provider. This fi eld on the WCC3 System Parameters
Screen is limited to 52 total characters for the E-mail address.

Alarm Type:

There are 5 Alarm types that can be programmed to send out an
Alarm E-mail to specifi c E-mail address.

Disabled by

The Disabled by fi eld is used to enable or disable the specifi c alarm
type. (Remember that there can be 4 pages of E-mail addresses.)
An “ON” or “1” disables the E-mailing of the Alarm type Callout
function per E-mail address. An “OFF” or “0” enables the E-mailing
of the Alarm type Call-out function per E-mail address.

This “Disabled by” fi eld can be programmed with the following:
0 (OFF), 1(ON), WXXX (Week Schedules), SXXX (Optimal
Starts), GBXXX (Global Binaries), new day, new hour, new min,
GCXXX, GHXXX, GLXXX (Tenant Override groups), LOCSET
(Local Set Mode), TEST (TEST Mode), / = / / / / (For Null value).
Just remember that the / / / / is a Null function that is neither “ON”
or “OFF”, but is generally treated as “OFF” condition but not
always.

Email Address

The E-mail Address fi eld on the WCC3 System Parameters Screen
is the E-mail address that you want send the specifi c WCC3 Alarm
E-mail that is based on Alarm type 1 to 5. There can be up to 12
E-mail address per alarm type.

This E-mail Address fi eld on the WCC3 System Parameters Screen
is limited to 50 total characters for the E-mail address.

1st, 2nd, 3rd Email Address

The “1st” E-mail Address is the primary or the fi rst E-mail address
that the WCC3 alarm type (1 to 5) will send an E-mail alarm to.

The “2nd” E-mail Address is the secondary or second E-mail
address that the WCC3 alarm type (1 to 5) will send an E-mail to
after sending the fi rst E-mail of the alarm type.

The “3rd” E-mail Address is the tertiary or third E-mail address
that the WCC3 alarm type (1 to 5) will send an E-mail to after
sending the second E-mail of the alarm type.

NOTE:

On only the fi rst 3 alarm class 1 E-mail addresses

on page 1 of the System Parameters Screen will receive an

automated Satellite Off System (SOS) E-mail message that is

sent out to these 3 E-mail addresses when a Satellite controller

or multiple Satellite Controllers goes off line (SOS). See

the Alarms section of this manual for more information on

Satellite alarms.

Repeat

The “Repeat” function is time in minutes to send out a repeated
E-mail after the fi rst e-mail is sent, and keep repeat sending
this E-mail every “X” amount of minutes until the alarm is
acknowledged.

Delay

The “Delay” function is time in minutes before the E-mailing of
the alarm to the 2nd and 3rd E-mail addresses after the E-mail is
sent to the 1st e-mail address.

System Parameters Screen