17. Binary Input w/Time Delay Board Installation

WCC III Technical Guide

17-2

SAT III CONTROLLER

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3 4

2

1

3 4

5 6 7 8

5 6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX

0-15VDC
OUTPUT

MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY

WCC3 BINARY IN W/ TIME DELAY

WATTMASTER CONTROLS, INC

YS102072 REV 2

24VAC

120VAC

TO OTHER
SAT III OR TO
WCC III - MCD

CONNECTION FROM A SAT III CONTROLLER TO WCC3 BINARY INPUT W/TIME DELAY BOARD USING THE "NEW" HSS CABLE CONNECTION METHOD

HSS CABLE - ORDER STANDARD LENGTHS OF 1 FOOT, 1.5 FOOT, 3 FEET, 25 FEET, 40 FEET, 80 FEET AND 120 FEET MAX

24

VA
C

GN
D

TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"

UP TO TWO WCC3 BINARY INPUT W/TIME
DELAY BOARDS MAY BE WIRED TO THE

SAT III CONTROLLER USING THIS

METHOD. CONNECT THE FIRST WCC3
BINARY INPUT W/TIME DELAY BOARD
HSS PORT TO THE SAT III CONTROLLER
HSS COMMUNICATIONS PORT, AND
THEN CONNECT THE FIRST WCC3
BINARY INPUT W/TIME DELAY BOARD
TO THE SECOND WCC3 BINARY INPUT
W/TIME DELAY BOARD VIA THE SECOND
HSS PORT ON THE FIRST WCC3 BINARY
INPUT W/TIME DELAY BOARD .
ADDITIONALLY UP TO TWO BINARY
OUTPUT / V-OUT BOARDS MAY ALSO BE
CONNECTED TO THE SAT III
CONTROLLER HSS PORT.

BINARY INPUT BOARD GETS POWER AND COMMUNICATIONS TO AND FROM THE SAT III FROM THIS HSS CABLE

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3 4

2

1

3 4

5 6 7 8

5 6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

CH

I

10

A

250

V

A

C

~

5A

30

V

D

C

SA

VDE

G

5Q

-1A

4

OM

R

O

N

DC

2

4V

C

H

IN

A

C~

DC

SA

VDE

N

EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX

0-15VDC
OUTPUT

MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY

WCC3 BINARY IN W/ TIME DELAY

WATTMASTER CONTROLS, INC

YS102072 REV 2

24VAC

120VAC

TO OTHER
SAT III OR TO
WCC III - MCD

CONNECTION FROM A SAT III CONTROLLER TO WCC3 BINARY INPUT W/TIME DELAY BOARD USING THE "NEW" HSS CABLE CONNECTION METHOD,
BUT USING THE HSS CABLE AS A POWER ONLY CONNECTION TO THE WCC3 BINARY INPUT W/TIME DELAY BOARD AND IGNORING THE HSS
COMMUNCATIONS TO AND FROM THE SAT III CONTROLLER.

HSS CABLE - ORDER STANDARD LENGTHS OF 1 FOOT, 1.5 FOOT, 3 FEET, 25 FEET, 40 FEET, 80 FEET, 120 FEET MAX

DRY INPUT CONTACTS ONLY
CONTACT CLOSURE TO GROUND
ONLY. NO 24VAC/VDC INPUTS

24

VA
C

GN
D

TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"

BINARY INPUT BOARD GETS POWER ONLY FROM THIS HSS CABLE. COMMUNICATIONS ARE IGNORED

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE
BINARY INPUT BOARD - GROUND
CONNECTIONS MUST BE THE SAME.

SAT III CONTROLLER

PIN #1

ST

RI

PE

IS

PIN

#1

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE
BINARY INPUT BOARD - GROUND
CONNECTIONS MUST BE THE SAME.

SAT III

HSS PORT

SAT III

HSS PORT

PIN #1

120VAC WIRING IS BY OTHERS

THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC3 BINARY INPUT BOARD IS 5 VA.

UP TO TWO WCC3 BINARY INPUT W/TIME
DELAY BOARDS MAY BE WIRED TO THE

SAT III CONTROLLER USING THIS

METHOD. CONNECT THE FIRST WCC3
BINARY INPUT W/TIME DELAY BOARD
TO THE SAT III CONTROLLER'S COVER
MOUNTED L1 TO L8 DIP SWITCH BINARY
INPUTS, AND THE SECOND WCC3
BINARY INPUT W/TIME DELAY BOARD
TO THE SAT III CONTROLLER'S COVER
MOUNTED L9 TO L16 DIP SWITCH
BINARY INPUTS.

120VAC WIRING IS BY OTHERS

THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC3 BINARY INPUT BOARD IS 5 VA.

REPLACE THE DIP SWITCH IN THE

SAT III CONTROLLER'S COVER WITH
THE RIBBON CABLE. OBSERVE

POLARITY OF PIN # 1
CONNECT PIN 1 TO PIN 1 AS SHOWN

DRY INPUT CONTACTS ONLY
CONTACT CLOSURE TO GROUND
ONLY. NO 24VAC/VDC INPUTS

Installation Instructions