WCC III Technical Guide

3-157

WCC3.EXE SCREEN DESCRIPTIONS

Range

The system has the capability of generating an alarm if the value
of this global analog is either inside or outside of the desired range.
If inside is selected, an alarm will be generated when the value of
the global analog is within the two limits specifi ed. If outside is
selected, an alarm will be generated if the value of the global is
outside the limits specifi ed.

Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:

<None, Inside, Outside>

Make your selection by pressing the

<space bar>

until the desired

data pattern has been selected and then press

<Enter>

.

Low Limit High limit

The Low and High Limits can be either an Address or a Value.
When you move the cursor to this fi eld, the word Address or Value
will appear. Since this is a choice fi eld, press the

<Space Bar>

until the desired choice appears and then press

<Enter>

.

If you select “Value” as the choice for this fi eld, you can enter a
number which will serve as the alarm limit.

If you select “Address,” you can specify an address such as an
analog input or global analog to be used as the alarm limit.

Analog Global Multi-Proportion Mode Screen

Type

Specifi es the priority (or “importance”) level for any alarms
generated by this input. Alarm types range from one (highest
priority) to eight (lowest priority). The system displays and e-mails
higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5)
have e-mail-out-on-alarm capabilities.)

Message #

Specifi es a message number which is used by the system to reference
a message which is entered on the Alarm Message Screen.