WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-174

In Local Set this global defaults to _____.

Specifi es the state (or value) of the binary global when the satellite
is in the Local Set mode. The satellite is in local set when it has lost
communications with the front end computer.

Since the fi rst fi eld is a “choice” fi eld, the list of available choices
will be displayed at the bottom of the screen:

<Off, On, Last Value>

Make your selection by pressing the

<space bar>

once for each

choice until the desired contact state has been selected, and then
press

<Enter>

.

------------ALARM-------------

Set Condition: None Type: 0

Message 0

The system has the capability of generating an alarm if the value of
this binary global is either ON or OFF.

Set the condition to “None” to not generate an alarm whenever the
Binary Global is Off or On. Set the condition to “On” to generate
an alarm whenever this Binary Global is On. Set condition to “Off”
to generate an alarm whenever this Binary Global is Off.

Because this is a choice fi eld, the list of available choices will be
displayed at the bottom of the page.

<None, Off, On>

Make your selection by pressing the

<space bar>

once for each

choice until the desired event type has been selected, and then
press

<Enter>

.

Type specifi es the priority (or “importance”) level for any alarms
generated by this input. Alarm types range from one (highest
priority) to eight (lowest priority). The system displays and e-mails
higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5)
have e-mail-out-on-alarm capabilities.)

The message number corresponds to a message on the ON/OFF
Message Screen
.

Binary Global One Shot Mode Screen