WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-132

Sampling From:

The value of the global analog will be the accumulated total of this
input over the specifi ed time period.

For example, if GA20 is input here, the system will periodically
read the value of analog global #20. The value of the global analog
will be the accumulated total of the readings over the specifi ed
time period.

Automatically reset by GB1 being ON

This allows you to have the system automatically restart the
accumulation cycle when a binary value goes either ON or OFF.
Because this second fi eld is a “choice” fi eld, the list of available
choices will be displayed at the bottom of the screen:

<OFF, ON>

GLOBAL ANALOG - INTEGRAL MODE -

ACCUMULATION MODE SCREEN

ANALOG

Global

#:

32

Name

is

GA32

Description: Integral

Data Pattern: xxx.x

Unit

of

Measure:

7

Gal

In Local Set this global defaults to LAST VALUE

Mode

3:

Integral

Sampling from : 1A2

Automatic Reset by ..... being ON

Sampling rate: 1 Minutes

Window: 24 Hours

Mode: Accumulation

Divisor: 1

i

=

n

Global value =

(  Di/n) / divisor

i

=

1

If sampling data is unavailable, then use 50 as default value

---------------Alarm---------------

Range Low Limit High Limit

Type Message # Message

None

Reset random data by pressing <Ctrl> <R> after editing.

HOME for menu

Make your selection by pressing the

<space bar>

once for each

choice until the desired mode type has been selected, and then
press

<Enter>

.

Sampling Rate: 1 Minutes

Window: 24 Hours

Assume we are monitoring fuel oil usage in gpm, and 1 minute is
entered as the sampling rate and 24 hours is entered for the Window.
The system will read the value of the fuel oil usage rate (gpm)
every minute and then add the current value to the accumulated
total until 24 hours have elapsed. After 24 hours, the calculation
process will start over.

The sampling rate can vary from 1 minute to 99 hours. The window
will accept from 0-999 minutes, hours, days, or samples.

Analog Global Screen’s WCC III Logical Address is GAXXX, where GA = Global Analog and XXX = Global Analog Address

Analog Global Integral Mode Accumulation Mode Screen