WattMaster WM-WCC3-TGD-01B User Manual

Page 834

Advertising
background image

Analog Input Screens

Programming a SAT 3F Satellite

so that Control Points can be

used in Global Calculations or

for Trend Logging

The SAT 3F controller can allow each TUC/VAVZ II controller to have
up to 8 Analog logically addressable control point values and 8 Binary
logically addressable control point values that can be globally used within
the WCC III program. These addressable control points are “shoehorned”
into the existing satellite data structure. As such, there can only be 16
TUC/VAVZ II (addressed 1 through 16) type controllers connected via
the TUC communications loop to the SAT 3F controller. Each one of the
SAT 3F controllers takes up 4 physical satellite addresses.

Figure 16: Analog Input Summary Screen

30

VAV/Zone Controller Actuator Package Technical Guide

Programming a SAT 3F

Advertising
This manual is related to the following products: